Consultar ensayos de calidad
Aire acondicionado - CASE STUDIES
ABSTRACT This paper discusses the design of
ventilation systems for negatively and positively pressurized patient isolation
rooms. The paper focuses on how to quantify and achieve target levels of
protection for either the patient (positively pressurized rooms) or health care
workers and other hospital occupants (negatively pressurized rooms). Attention
is paid to the influence of ceiling supply diffuser selection. Thermal comfort
issues are also discussed, and an alternative to “age-of-air”
techniques using age-of-contaminant calculations is recommended for use in
patient isolation room design. Practical considerations are illustrated through
the presentation of two case studies. The first case study of a TB isolation
room includes a CFD model analysis of different air distribution systems including
an assessment of ventilation effectiveness and patient thermal comfort. This
work includes simulation of a cough from a patient toward a health care worker
and throughout theisolation suite. The second case study of a positive pressure
isolation room assesses the throw of supply air around a patient bed in terms
of providing protection for the patient while maintaining comfortable
conditions. INTRODUCTION Challenges to health services around the world from
monkey pox, severe acute respiratory syndrome (SARS), and continued cases of
tuberculosis have meant that hospitals have had to deal with, and prevent the
spread of, contagious diseases. Additionally, health care facilities are
providing for people afflicted with diseases that suppress a patient’s immune
system, either through the treatments (e.g., cancer) or due to
the illness itself (HIV/AIDS). To provide adequate protection of patients and
caregivers, special purpose patient isolation rooms are designed with
ventilation systems that maintain a negative pressure to protect caregivers or
positive pressure to protect patients. While positive or negative
pressurization can be used as a containment strategy, it leaves the occupants
within the room (caregivers and patients) with risks from each other. Proper
ventilation design can help to reduce those risks by providing either
deflection of contaminated air or at least efficient removal of contaminants.
The momentum from the supply diffuser can be used beneficially in this regard
or, as often happens without careful design, can aggravate the problem. The
case studies that follow illustrate some of the effects of supplymomentum,
buoyancy, and room dimensions on ventilation within the space. BACKGROUND The
purpose of this section is to review the means by which airborne infections
spread, using tuberculosis (TB) as an example, and then present methods by
which patient room ventilation systems are assessed. In that review,
comparisons between the different methods are provided. TB Isolation Rooms
(Case 1) Infectious diseases can spread from one person to another by aerosol
droplets. The spread of tuberculosis (TB), for example, occurs when an
otherwise healthy individual inhales a sufficient number of tubercle bacilli
that are expelled by a patient infected with pulmonary TB. An infected patient
continuously expels these particles when coughing, sneezing, talking, or
spitting (Gammaitoni and Nucci 1997). The infec-
Duncan Phillips is an associate and senior specialist, Ray Sinclair is a
principal and project director, and Glenn Schuyler is a principal and
vice-president of research at Rowan Williams Davies and Irwin, Inc., Guelph, Ontario,
Canada.
IAQ 2004
1
tious particles are estimated to be on the order of 1 to 5 µm in
size (CDC 1994) and normal room air currents can keep them airborne for long
periods of time. These particles are easily spread about a room or building
unless adequate protection and control are provided. A number of outbreaks of
TB in hospitals in the 1980s and 1990s (Conroy et al. 1997) prompted the CDC to
issue a number of reports regardingthe prevention of TB transmission in health
care facilities (CDC 1994). Infected patients are isolated from other
individuals in hospitals and placed in special isolation rooms. A series of
administrative and engineering controls are implemented to reduce airborne
transmission. The administrative controls as described by CDC (1994) and
summarized by Conroy et al. (1997) include (1) an infection control program
identifying individuals likely infected, (2) training, (3) medical surveillance
of at-risk health care workers, and (4) respiratory protection for those in
immediate contact with infected patients. The engineering controls recommended
include: (1) the room be at least 0.001 in. w.c. negative pressure with respect
to adjacent spaces; (2) airflow should be designed for and tested such that it
travels from hallways or anterooms into the patient room; (3) the exhaust flow
should exceed supply air by 10% or a minimum of 50 cfm within the patient
isolation room; (4) the velocity under the door when it is closed should be a
minimum of 100 fpm; and (5) the dilution ventilation rate should be at least 6
ACH and 12 ACH in newer facilities (Conroy et al. 1997). The basic design
philosophy of TB patient isolation rooms is relatively straightforward: a high
ventilation rate within a room is used to dilute and flush the aerosol
contaminants. ASHRAE (2003) notes that “the preferred
design approach [to airborne infectious isolation rooms] emphasizes air
mixingeffectiveness and dilution ventilation without attempting to establish
unidirectional airflow.” The objective here is to maximize the
mixing rate. Efforts are made to prevent the airborne contaminants from
escaping the room by ensuring a net flow into the room at all times and in some
cases the presence of an anteroom serves as an airlock. In cases where it is
not possible to provide adequate dilution, or where additional preventative
measures are desired, HEPA filtering (Gammaitoni and Nucci 1997) and ultraviolet
germicidal irradiation (UVGI) (Memarzadeh and Jiang 2000) can be used to remove
or kill the viable TB bacilli. The UVGI assessment is reported in more detail
in NIH (2000). The required performance of a patient isolation room ventilation
system is related to providing adequate dilution to minimize the risk that a
caregiver may be exposed to an infectious dose. Kowalski et al. (1999) provide
references that suggest that the infective dose for M. tuberculosis is between
1 and 10 bacilli. Given that the number of aerosol particles in the 1 to 5 m
aerosol particle range released by a sneeze is on the order of 100,000 and a
cough on the order of 1,000 particles (Duguid [1945] as cited by Kowalski and
Bahnfleth [1998]), the dilution rate required in order to reduce the
2
concentration of particles below 10 is at least 100 and more likely 10,000 for
a single breath. Multiple coughs or sneezes and a prolonged exposure to the
contaminated air means thatthe dilution rate must be significantly higher.
Unfortunately, the use of a high ventilation rate in a room does not guarantee
that all regions of the room are ventilated at a high rate. Stagnant zones,
isolated corners, and shortcircuiting can lead to a reduction in ventilation
efficiency and, as a result, lower ventilation rates in large sections of a
ventilated room. Some close proximity CFD modeling work has been conducted in
the past. Bjørn and Nielsen (1998) report CFD simulations of the
transport of gases between two people breathing and how they compare to physical
experiments using breathing manikins. Bjørn and
Nielsen (1998) report that while it was difficult to match the CFD simulation
to the data, the simulations did permit them to assess the sensitivity of the
results to various room configurations. They determined that the
convective heat outputs of the individuals, crosssectional exhalation area
(size of mouth opening), and pulmonary ventilation rate were all important
factors in the level of contamination from one person to another. The distances between the manikins was comparable to that of a
health care worker tending to a patient. Their results also indicated that the
simulated exposure is not very sensitive to variations of exhalation
temperature at small mutual distances but is more so as the distance increases.
In this paper, a study is presented of ventilation conditions in a TB isolation
room. The purpose of the CFD modelingcarried out was to assess the efficacy of
the ventilation in a typical room planned for construction at an existing
health care facility. The goal of the assessment was to determine the level of
protection afforded health care workers by the ventilation system under varying
operating conditions (heating and cooling modes) and system configurations and
supply diffuser types. The design objectives were to achieve a local
ventilation rate of 12 or greater in all parts of the room with a volumetric
supply air change rate of 15 ACH or less to the room. Given the mixing type of
ventilation system implemented, this requires that the stagnant zones be
eliminated. It may be necessary to have a dilution rate within the room of at
least 100,000:1 in order to reduce the number of aerosol particles at the
health care worker’s face from multiple coughs to which they may be
exposed over a period of time. This dilution rate between the patient’s
mouth and the health care worker was known to be unachievable. That said, it
was of interest to know what levels of dilution are likely and whether the
different ventilation configurations play a role in this close proximity
dilution. Of equal importance was the concentration of particles in the
vicinity of the door. If the door region were contaminated with particles, some
may escape into the hallway when the door is opened, since no anteroom was
planned for the isolation rooms in this facility.
IAQ 2004
Positive PressurePatient Isolation Room (Case 2) A
second type of patient room is one in which the care is provided to patients
who are immuno-suppressed. In these rooms, the ventilation system of the room and
connected spaces are configured to prevent air from entering the room through
any means except the room ventilation system. The ventilation system in the
room is typically configured with HEPA filters for the incoming air and the
room is positively pressurized with respect to the adjacent spaces. It is
common for these facilities to have significant ventilation rates (e.g., 15
ACH) and thus the risk of drafts is high. Complaints of drafts are common in
facilities of this type, and experience suggests that improper sizing and
placement of ceiling diffusers can lead to draft. These patients are often in
residence for a period of months, and maintaining comfort is important. In a
recent report, Memarzadeh and Manning (2000) present a summary of research in which
36 different numerical experiments of a patient room were conducted. These
numerical experiments tested different seasons (winter and summer) and
different diffusers and ventilation rates. The results suggest that for summer
conditions, the diffuser combination, return location, and ventilation rate do
not have a significant effect on the overall acceptability of the room. They
used ageof-air distributions to assess the efficiency of the ventilation
system, thermal comfort to assess the conditions for an occupant,and the Air Diffusion Performance Index (ADPI) as a measure
of uniformity of conditions. The ventilation patterns for a winter scenario
were more variable, and minimum ventilation rates of 6 ACH were recommended
along with baseboard heating. The Role of CFD Modeling The design of air
distribution systems in patient isolation rooms can be greatly assisted by
computer simulations based on computational fluid dynamics (CFD) modeling. CFD
can predict air velocities, temperatures, and contaminant concentrations
throughout the room for a range of design challenges. This information can be
interpreted in terms of indoor air quality indices that can be compared against
health criteria and also thermal comfort indices to assess patient comfort.
Supply diffuser locations and types, flow rates, exhaust air vent locations,
distributions of heat loads in the room, arrangements of furniture, and other
blockages to air movement can be assessed and comparisons made to judge the
best design alternatives. The theoretical details are that CFD is a numerical
simulation technique in which the standard equations of fluid flow representing
the conservation of mass, momentum, and energy are solved. For most practical
environmental and engineering flows, equations imposing the effects of
turbulence are required. Finally, the transport of a contaminant, in this case
representing a cloud of light particles released during a cough, can be
included. In fact, even individualparticle trajectories can be predicted if
necessary. Many authors have included a review of CFD techniques, including
Patankar (1980), Chen and Srebric (2001), and Jiang et al. (2003). The
IAQ 2004
simulations presented here have been conducted using two different commercial
CFD packages. Age-of-Air Analysis The use of age-of-air techniques to assess
indoor environmental flows was introduced to the ventilation field by Sandberg
and Sjöberg (1983). Since then it has been put into practical form by many
authors including Sutcliffe (1990). It is an analysis technique that parallels
the residence time techniques used in chemical engineering. It permits one to
assess how fresh the air is at a location within a ventilated space or the
average age of the air leaving the room. If some region of the room has an
age-of-air that is greater than the average age-ofair leaving the room, then it
is underventilated. If the age-ofair within the room is uniform and equal to
that at the exhaust, then the room is well mixed. A number of indices have been
developed for age-of-air analysis and these may be found in ASHRAE (2001).
These are frequently used to assess comfort or the effectiveness with which the
HVAC system distributes the supply air for a variety of ventilation
environments including patient rooms. Age-of-air-based ventilation indices
typically report how a ventilated environment compares to a space that is
either perfectly mixed or one with that has plugdisplacement flow. A notable
difficulty in using the indices is that there has been a set of slightly
different terminology used for similar indices – the terms ventilation
efficiency and ventilation effectiveness have been used interchangeably when
they should not be. ASHRAE (2001) provides a definition of air change
effectiveness, and it is this index that the authors have used.
Age-of-Contaminant The use of age-of-contaminant to
assess ventilation flows is less common. It is based on the premise that a
contaminant is released at a location in a room and potentially travels about
the space and is then removed from the space by the ventilation system. The
rate at which the contaminant concentration is reduced at various locations
within the space provides information on the ability of the ventilation system
to flush the space. The rate of flushing in any particular region provides
information about the amount of fresh air entering that region. Brouns and
Waters (1991) provide a summary of the technique. In a manner similar to
age-of-air analysis, the age-ofcontaminant calculations can be expressed in
terms of indices. Brouns and Waters (1991) list the contaminant removal
effectiveness as one index that can be used for the assessment of contaminant
transport about a room. In a review of different indices for assessing
ventilation environments, Novoselac and Srebric (2003) conclude that for rooms
in which the contaminant source or strength is unknown, theage-of-air indices
are appropriate. However, in cases where the contaminant source location and
strength is known, age-of-contaminant indices are more informative in communicating
information about contaminant removal effectiveness. Contaminant removal
effectiveness is defined
3
by Brouns and Waters (1991) to be the ratio between the nominal time constant
for the ventilation air and the nominal time constant for the contaminant. The
contaminant removal efficiency is then a manipulation of the effectiveness.
These parameters for a particular room configuration are typically compared to
values for perfect mixing and plug flow. The air change effectiveness is
defined as a ratio between the nominal time constant and the room average
age-of-air. Local air change effectiveness can be calculated if the local
age-of-air is used instead of the room average. Thermal Comfort To predict thermal comfort conditions, different models have
been developed or adopted by various recognized authorities. ASHRAE (2001)
promulgates the Fanger (1972) Predicted Mean Vote (PMV) comfort index to
predict thermal comfort. This is consistent with ISO 7730 (ISO 1984). This
numerical manipulation of air speed, temperature, humidity, occupant clothing,
work output, activity, incident radiation, and turbulence intensity predicts a
thermal sensation scale that can then be interpreted. Thermal comfort
assessment of ventilated environments is common, including those for patients.
Other comfortindices such as the Air Diffusion Performance Index (ADPI) (ASHRAE
1990) may be used to assess comfort; however, the drawback with this index is
that it does not include activity level, clothing, radiant conditions, or
relative humidity as part of the assessment. For the simulations presented
here, thermal comfort plots using the PMV scale have been generated assuming
that the patient’s activity level is 0.7 (ASHRAE 2001), which is
equivalent to sleep, and work level was assumed to be nil. Furthermore, the
patient was assumed to be wearing a short-sleeved hospital gown with a light
blanket cover. The clothing level was then adjusted by 0.25 due to the presence
of the bed, yielding a total value of 1.3. It is also assumed that the relative
humidity is 50%. Summary of Background One objective of the background section
was to discuss means by which patient isolation rooms can be assessed. Some of
the key points from this review include: 1. Patient isolation rooms may be
assessed to determine whether the patient and/or other occupants will perceive
the room to be comfortable or express discomfort. It is possible to use
modeling tools to assess the potential risk of exposure to occupants in or
around patient isolation rooms. Some assessments of isolation rooms have
evaluated the efficacy of UVGI as part of a contaminant containment strategy.
Patient isolation rooms have also been assessed from the perspective of
age-of-air. This allows a determination of howwell the ventilation air is distributed
within the room.
A more appropriate means of assessing the ventilation system in a TB isolation
room could be to assess the contaminant removal efficiency. This could also be
applied to a positive pressure isolation room where the contaminant source is
untreated outside air through a temporarily open door or another source such as
window leakage.
CASE STUDIES
Case 1: TB Isolation Room The ventilation assessment of the TB isolation room
presented here takes the reader through details about the room configuration,
CFD model simulation process, age-of-air and age-of-contaminant calculations,
thermal comfort assessments, and the predicted dilution of a patient cough. The
primary conclusion that the reader may find interesting is that the standard age-of-air
analysis has notable limitations and that the prediction of age-of-contaminant
is helpful in comparing proposed ventilation strategies. Room Description,
Loads, and Ventilation System Configuration Three simulations are presented
here; they show the predicted conditions representing a laminar diffuser
arrangement and two different throw patterns for the square diffusers. The
first has the diffusers acting as four-way diffusers. The second has the
diffusers acting as two-way diffusers. The HVAC arrangements are compared on
the basis of the age-ofair and relative concentrations of aerosol particles
expressed as dilution ratios at the face of the healthcare worker following the
cough. The layout of the TB isolation room is presented in Figures 1 and 2 for
an HVAC configuration using laminar and square diffusers, respectively. The
room itself had a floor plan of approximately 16.26 m2 (175 ft2) and was
approximately 46.72 m3 (1650 ft3) in volume. The heat loads and boundary
conditions applied to the room for the different HVAC configurations were the
same and are summarized in Table A1 in Appendix A for the summer design case.
The HVAC flows into and out of the room are summarized in Tables A2 and A3 for
the laminar diffusers and square diffusers (two- and four-way), respectively.
The flows in the tables represent a global ventilation rate of approximately 15
ACH. Assessment Methodology. The CFD process is
briefly described in Appendix B. The results of this process were a prediction
of the steady-state flow field for each of the diffuser arrangements from which
age-of-air, age-of-contaminant, and thermal comfort analyses were conducted. An
additional method of assessing the ventilation efficiency in the room was to
model a cough. This was achieved by implementing a release of contaminant from
the mouth of the patient at 3.56 m/s (700 fpm), which emulated a cloud of light
particles. These transient (time-varying) simulations were conducted by
starting with a solved steady-state flow
IAQ 2004
2.
4.
4
IAQ 2004
Figure 1 TB isolation room layout and boundary conditions for laminardiffuser
configuration.
5
6
Figure 2 TB isolation room layout and boundary conditions for square 2 and
four-way diffuser configurations.
IAQ 2004
Figure 3 Region of TB isolation room with age-of-air > 300—laminar
diffuser configuration.
Figure 4 Region of TB isolation room with age-of-air > 270—square
four-way diffuser configuration.
field for the room. Using a transient solver, the
patient’s mouth was then turned into a source of air laden with
particles. At 0.15 second after the start of the cough, the flow from the mouth
was stopped. The particle concentrations were then monitored at various
locations in the room. The most important locations can be considered to be the
health care worker and locations near the door. The pulsed release of a tracer
representing a cloud of aerosol particles permits one to assess the contaminant
removal efficiency of the different ventilation configurations. Age-of-Air and
Thermal Comfort Figures 3, 4, and 5 present iso-surfaces of age-of-air at 300,
270, and 300 seconds for the laminar and square diffusers, four-way and
two-way, respectively. The square four-way diffuser room configuration resulted
in an air flow pattern that had a maximum age-of-air within the room of
approximately 280 seconds. Regions inside the iso-surface have relatively stale
air. Those outside the surface have air that is predicted to be fresher than
the threshold value identified for the isosurface. The figures show that
thelaminar (Figure 3) and square diffusers configured for a two-way throw
(Figure 5) do not meet the ventilation efficiency criterion of having the
ageof-air at all locations within the room at 300 seconds or less. In fact, it
is very difficult to meet this form of ventilation criterion unless the room is
either very well mixed with an air change rate greater than the target
criterion or employs a displacement ventilation system. The thermal comfort in
the two rooms for the patient was essentially the same. The PMV values were
0.65 (slightly warm) and 0.46 (comfortable) for the laminar and square fourway
diffusers, respectively. The reason that the displacement diffuser setup
resulted in a sensation of slightly warm was that the temperature over the patient
is predicted to be slightly higher. The four-way diffusers do a better job of
penetrating the cooler supply air into the patient region.
IAQ 2004
Figure 5 Region of TB isolation room with age-of-air > 300—square
two-way diffuser configuration.
Dilution of Cough Figures 6 and 7 present the time-varying concentration of
particles at various locations for the laminar and four-way square diffusers
for the first 60 seconds. The concentrations have been scaled to a reference
concentration of 10,000 at the mouth of the patient. Thus, a concentration of
10 at any given location represents a dilution of 103. A monitor was
established in the path of the cough approximately 0.12 m (4.75 in.) from the
patient’smouth. The locations identified as near the door region are 0.61
m (2 ft) from the face of the door, 0.91 and 1.52 m (3 and 5 ft) high. The
plots show that the concentration peaks at the mouth of the health care worker
at approximately 5 seconds of the cough and rapidly tails off for both
ventilation strategies. The peak magnitude of the cough does not change
significantly for the two strategies. The inset graphs in Figures 6 and 7 show
the concentrations for a 10-minute duration. In
addition to the concentrations at each location, the concentration for a hypo7
8
Figure 6 Particle concentration for laminar diffuser
configuration.
IAQ 2004
IAQ 2004
Figure 7 Particle concentration for square four-way diffuser configuration.
9
Table 1. Peak Concentrations and Accumulated Dosages for the Laminar and
Four-Way Square Diffuser
Location Cough path 6 in. above desk 3 ft above floor near door 5 ft above
floor near door At health care worker’s mouth 1 ft above patient
Perfectly mixed room
* †
Peak Concentration* Laminar Square 4-way 6190.0 0.126 0.017 0.017 43.6 26.2
0.097 6187.8 0.120 0.307 0.483 46.3 3.1 0.097
Accumulated Dosage † Laminar Square 4-way 1275.8 26.3 7.5 7.9 212.6 155.2
22.9 1275.8 (not a typo) 22.3 26.0 27.5 182.2 56.1 22.9
The units of concentration are [cough particles/cough volume]. The units of
accumulated dosage are [cough particle seconds/cough volume].
thetically perfectly mixed room was also included
onthese plots. The inset plot in Figure 7 shows how the distribution of cough
aerosols for the four-way diffuser room design approaches the perfectly mixed
result at approximately 3 minutes for the locations monitored. However, the
inset plot in Figure 6 highlights how the aerosol in the laminar flow room
requires up to 8 minutes to approach conditions that
would reflect a well-mixed room. These plots also permit one to evaluate the
time it takes for aerosol to reach the door region of the two rooms. For the
fourway square diffuser, the cough aerosol reaches the door in approximately 35
seconds (for a particle concentration of 0.01). The results for the laminar
diffuser configuration highlight how the lack of induced mixing significantly
increases the time it takes for the aerosol particles to reach the door—
approximately 120 seconds are required for the same concentration to reach the
door. Table 1 summarizes the maximum cough particle concentrations, as well as
the accumulated dosage over 10 minutes, for individuals located in the regions
monitored during the course of the cough dilution. In addition, the peak
concentration and accumulated dosage for the perfectly mixed room are presented
for reference. It has been assumed that the individuals are not moving during
the period of dosage integration. While it may be unrealistic to assume people
are motionless for 10 minutes, the integration of dosage does provide a useful
measure for exposure to coughparticles at each location monitored. It is clear
from Table 1 that there are consequences to the selection of the diffuser type
that are not evident until one assesses the time-varying particle concentrations.
For example: • The rapid mixing of the square four-way diffusers does not
reduce the concentration of particles at the health care worker’s head.
However, the peak concentration near the door jumps up by an order of
magnitude.
•
•
Neither the peak concentration nor accumulated dose along the cough path is
influenced by the diffuser selections modeled here. The effect of having
laminar diffusers in the near door region appears to help to prevent the
particle laden air from penetrating into the door region – the peak
concentrations and accumulated dosages are less than those for the perfectly
mixed room. However, the region is poorly ventilated by fresh air, as indicated
by Figure 3.
Comparison of both the laminar and square four-way diffuser to the perfectly
mixed room conditions suggests that the room HVAC layout could be improved. One
additional observation of the time-varying concentrations is that the room
exhaust did not start to evacuate the cough particles in any great
concentration for approximately 27 seconds for the laminar diffuser
configuration and 40 seconds for the fourway square diffusers. Clearly, this is
a specific result of the room configuration; however, it does highlight the
importance of the interaction between thediffusers and the exhaust. This would
explain the reason why the accumulated dosages are larger for the two rooms
than the perfectly mixed equivalent. The cough particles in a perfectly mixed
room would start to leave the room as soon as they had been generated, reducing
the total number of particles in the room available for inhalation. Table 2
compares the contaminant removal efficiency and the air change effectiveness
for the two different TB room configurations. It highlights how age-of-air
indices alone can misrepresent the performance of a patient isolation room
ventilation system. The results in Table 2 show that while the air exchange
efficiency indices for both rooms is close to that for a perfectly mixed room,
the contaminant removal efficiency is far from it. This indicates that while
the room approaches well-mixed behavior, the cough location, along with the
locations of the receptors of interest as well as the acute nature of the
exposure, suggests that the air exchange efficiency is not a good measure of
the performance of a patient room ventilation system.
IAQ 2004
10
Table 2.
Location Cough path 6 in. above desk 3 ft above floor near door 5 ft above
floor near door At health care worker’s mouth 1 ft above patient Room
average Perfectly mixed room
Contaminant Removal Efficiency and Air Change Effectiveness
Contaminant Removal Laminar Square 4-Way 0.019 0.468 0.723 0.716 0.104 0.136
0.019 (not a typo) 0.509 0.474 0.460 0.120 0.301N/A 0.500 0.500 Air Change
Effectiveness Laminar Square 4-Way 1.10 1.01 1.32 1.08 1.09 1.09 1.13 1.00 1.25
1.12 1.29 1.33 1.20 1.18 1.25 1.00
Finally, the results presented for the cough simulations represent one
conceivable scenario of patient and health care worker location. If the source
of the cough were in another location in the room, then the exposure would be
somewhat different. However, the magnitude of the change for the fourway
diffuser room configuration would be less than that for the room with the
laminar diffusers for equivalent exposure locations. This is because the time
required for the concentration conditions in the laminar diffuser room to
approach wellmixed conditions is approximately eight minutes, while that for
the four-way diffuser case is three minutes; therefore, for most locations in
the room, the time to mix a release of cough particles around the rest of the
space is three minutes for the four-way diffuser and eight minutes for the
laminar diffuser. The cough location selection for the laminar diffuser room
will play a larger role in the resulting exposure. The results discussed above
demonstrate that a TB patient isolation room should be assessed using
age-of-contaminant analysis techniques rather than age-of-air indices. It is
possible for the age-of-air calculations to be misleading at the very least for
the circumstances presented here. Case 2: Immuno-Suppressed Patient Room In the
second case study, a positivepressure patient isolation room was designed in a
health care facility located in the U.S. Southwest. Here local codes require
that there be a minimum of 15 ACH provided to the room and that the supply and
return be arranged to minimize stagnation and short-circuiting. Part of the
objective for the design of the patient room described here was to change the
environment patients experience when subjected to long hospital stays. Patient
room pods were designed with a 32.05 m2 (345 ft2) multipurpose work alcove and
nurse and physician work areas that serve as the common air lock for six
patient rooms. This area is a negatively pressured space with respect to the
isolation rooms. The anticipated effect of this configuration would be that the
patients would feel more connected to other hospital occupants and not be
behind two panes of glass as is typically the case when the room has an
anteroom.
IAQ 2004
Figure 8 Positive pressure isolation room configuration with adjacent work
alcove.
As part of the design effort, a full-scale mockup of a typical patient room was
built. The mockup helped the design team assess the look, ergonomics, and
acoustics of the room, test building practices, and test working equipment and
systems. In order to better understand the details of the airflow patterns and
how these patterns may affect protection and thermal comfort of the patient, a
CFD computer model was developed. The CFD computer model was set up to test
conservativeworst-case conditions in the room including solar loads on a warm
summer day and equipment, lighting, and occupant heat loads. The simulations
were conducted to assess conditions with the isolation room doors open and
closed to evaluate the likelihood of air entering the room from adjacent spaces
and the potential for drafts or dead flow zones in the room. Figure 8 presents
the room configuration with the alcove attached. For the door-closed scenarios,
a surface was placed across the opening between the alcove and patient room.
The room was approximately 18.6 m2 (200 ft2). There were two HEPA filtered
radial diffusers located to either side of the
11
patient’s bed in the ceiling. The exhaust vent was wallmounted about 0.15
m (0.5 ft) above the floor, diagonally opposite the patient’s bed near
the door. As described above, the ventilation rate was 15 ACH. Blockages
representing the patient and a health care worker were incorporated into the model.
Additional blockages representing equipment and furniture were also included.
The two model studies in this project contained approximately 215,000 and
345,000 nodes for the door-closed and door-open scenarios, respectively. In
advance of running the patient room model, calibrations were carried out to
adjust momentum sources applied near the diffusers until a good match was
achieved between the model and the manufacturer’s information on throw
and spread of the air in a separate, open room test model.This effort was
similar to the work that is reported in Srebric and Chen (2003) and was
conducted before that report was available. The loads implemented in the room
were the patient and doctor sensible load (72 W/245 Btu/h each), equipment (495
W/1690 Btu/h), a television (150 W/510 Btu/h), lighting in the room (175 W/600
Btu/h) and in the bathroom (140 W/480 Btu/ h), a radiative solar load (1000
W/3415 Btu/h), and a convective solar load at the window (420 W/1435 Btu/h).
The total heating load for the door-closed simulation was 2524 W/ 8620 Btu/h.
The supply air temperature was 20.5°C. For the door-open scenario with the
work alcove included in the CFD model, additional loads for lighting, occupant,
and equipment heat (1045 W/3570 Btu/h total) were added; the loads within the
patient room remained the same. There was an additional four-way diffuser
located within the work alcove, and the supply air temperature for this
diffuser was set to balance the loads from the alcove and meet the same target
room temperature.
RESULTS Figure 9 presents the prediction of thermal comfort for the door-closed
configuration and indicates that the patient would be slightly cool. However,
the temperature at this level is reasonably uniform at 22.0-24.5°C
(71.6-76.1°F) with the warmer temperatures caused by the presence of some
portable medical equipment adjacent to the bed. The velocity plot, not included
in this paper, shows that air currents are low (
Política de privacidad
Física |
|
Balistica - Caracteristicas, Composición |
Cantidad de movimiento - Conservación de la cantidad de movimiento |
Fuerza - velocidad, coordinacion, flexibilidad, resistencia |
Propósitos y efectos de la aptitud física |
Pulsares - Un púlsar, El efecto combinado |
Calentamiento - Combustibles fósiles, Energía hidraulica, Energía Mareomotriz, Biomasa, Energía Solar, Energía geot |
Calor y cambios de fase del agua |
Ausentismo - los 10 ladrones de tu energía |
Caida de Tencion - Cálculos de los Conductores Tubería y Protecciones |
Curva tipica de ensayos de tension - Deformaciones elasticas, Fluencia o cedencia, Deformaciones plasticas |
|
|
|
|
|
|